Select Store:
Select Currency:

Sick UE10-30S2DO (6024917)

Product Summary

Safety Relay Module UE10-3OS2D0
Manufacturer: Sick
Manufacturer part number: 6024917
SKU: 151257
Weight(kg): 0.2750

Click here to check availability

Pricing - Condition Manufacturer New

Call for pricing
    • Ideal for applications with opto-electronic protective devices and safety controllers with OSSD outputs
    • Evaluation unit for a safe processing of OSSD output signals
    • 3 safety outputs, 1 application diagnostic output
    • Fast tool-free mounting/disassembly due to to pluggable terminals
    • Feedback signal for external device monitoring (EDM)

Your benefits

  • Offers all needed contact paths in a compact form
  • Fast diagnostics via the status information reduces downtime
  • Connects the advantages of classic relays and easy circuitry

 

Applications

Type of switching amplifier: Contact expansion module
Emergency stop pushbuttons: -
Safety switches: -
Safety Switch with mechanical lock: -
Two-hand control systems: -
Pressure sensitive mats: -
Opto-electronic protective devices:
Opto-electronic protective devices without RES/EDM: -
Opto-electronic protective devices with RES/EDM:
System part: Safety relays
 
Functions
Input circuit: Single- or dual-channel
Cross-circuit detection: -
Reset/restart: Automatic
External device monitoring: -
 
Technical data
Safety integrity level: SIL3 (IEC 61508), SILCL3 (IEC 62061) 1)
Category: Category 4 (EN ISO 13849) 2)
Performance level: PL e (EN ISO 13849) 3)
B10d parameter: 1.26 * 1E 06 switching cycles (AC-15, 230 V, I = 1.5 A)
5.9*1E 06 switching cycles (AC-15, 230 V, I = 0.75 A)
4.35*1E 05 switching cycles (DC-13, 24 V, I = 2.5 A)
1*1E 07 switching cycles (DC-13, 24 V, I = 0.63 A)
PFHd: 3.0 * 1E-08
TM (mission time): 20 a
Stop category: 0, EN 60204
Width: 22.5 mm
Contact type: Positively driven
Number of enable current contacts: 3
Number of signalling current contacts: 1
Type of output: Relay contacts
Rated operating current (voltage): 4 A (230 V AC) 360 switching cycles/h
3 A (230 V AC) 3600 switching cycles/h
4 A (24 V DC) 360 switching cycles/h
2.5 A (24 V DC) 3600 switching cycles/h
Maximum switching current: 6 A
Maximum total current: 12 A
Mechanical life (relay contacts): 1*1E 07 switching cycles
Electrical life (relay contacts): 2* 1E 06 switching cycles, dependent upon loading, details see operating instructions
Enclosure rating: IP 20
Ambient operating temperature from ... to: -25 °C ... 55 °C
Connection type: Screw-type terminals
1) 2) 3) If the feedback current path Y1 - Y2 (external device monitoring) is monitored using an appropriate main unit  
Products specifications
Manufacturer category Sick UE10
Manufacturer Sick